Standards Document Up for Review:

Standard 260-13 | Laboratory Methods of Testing Induced Flow Fans for Rating


Click the document title to purchase this item in our Online Store.

Comments:

Section/Figure/Table #: 9.2 Total Efficiency Calculation
Comments:
Due to upcoming changes with the DOE regulating fan efficiency it would be advantageous to put a note in this section as to why we calculate total efficiency differently than AMCA 210

Proposed Change:
Static efficiency is not used to rate this type of fan due to the need for creating a high velocity at the discharge, thus a modified total efficiency calculation is preferable which includes velocity pressure in the formula.

Kenneth Kuntz
Greenheck Fan
kenneth.kuntz@greenheck.com
Posted: November 11, 2016